Electrical Requirements
- All electrodes present at each structure shall be bonded together to form one grounding electrode system to include: Concrete Encased Electrodes (UFER), water piping, ground rings, grounding rods, and plate electrodes. Bonding shall ensure electrical continuity. The electrode conductor must be connected in an approved manner and inspected prior to concealing. (NEC 250.24, 250.28, 250.32, 250.50)
- All electrical receptacle, switch, light, and junction boxes shall be made up using proper mechanical connectors at time of rough inspections. This includes non-grounded, grounded, and grounding conductors.
- Tamper -resistant Receptacle outlets are required in every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room or similar dwelling areas, including attached and detached garages and accessory buildings to dwelling units, spaced so that no point measured horizontally along the wall line exceeds 6-feet from a receptacle outlet. (NEC 210.52, 406.3, 406.12)
A. Counters 12-inches in width or wider shall have receptacles placed no more than 20-inches above the countertop and spaced so no point exceeds 24-inches from a receptacle outlet.
B. Island and peninsula counters with a length at least 24-inches and a width of 12-inches or greater must be equipped with at least one outlet.
C. At least one receptacle outlet shall be installed in a bathroom within 36-inches of each basin.D. At least one receptacle shall be installed for laundry equipment, in unfinished basements, and in each car space of attached and detached garages. The branch circuit supplying the garage receptacles shall not supply outlets outside of the garage. (NEC 210.52(G)(1))
E. Not less than one receptacle that is readily accessible from grade level and located not more than 6 feet 6 inches above grade, shall be installed outdoors at the front and back of each dwelling unit having direct access to grade level. Balconies, decks, and porches that are accessible from inside of the dwelling unit shall have at least one receptacle installed within the perimeter of the balcony, deck, or porch.
F. Attics or crawlspaces containing equipment must be provided with at least one receptacle within 25-feet of the equipment.
G. Hallways of 10 feet or more in length shall have at least one receptacle outlet. The hall length shall be considered the length measured along the centerline of the hall without passing through a doorway. Foyers that are not part of a hallway and is greater than 60 square feet shall have a receptacle(s) located in each wall space that is 3 feet or more in width. Doorways, door-side windows that extend to the floor, and similar openings shall not be considered as wall space.
- A minimum of two 20-amp rated branch circuits shall serve receptacles in the kitchen, pantry, breakfast area, and dining area. At least one 20-amp branch circuit shall supply bathroom receptacles and at least one 20-amp branch circuit shall supply laundry. Refrigerator receptacle can be connected to one of the two required kitchen branch circuits or from an individual branch circuit rated 15 amperes or greater. (NEC 210.52(B))
- Ground fault protection shall be provided on all 125-volt through 250-volt single phase 15 and 20-ampere receptacle outlets installed in kitchens including butler’s pantries, bathrooms, garages and accessory buildings, outdoors, crawl spaces, basements, within 6’ of all other sinks, and laundry areas. Ground-fault circuit interrupters shall be installed in readily accessible locations. (NEC 210.8, 210.8(D))
- A. Combination type arc-fault circuit interrupters must be installed on all 120-volt 15 and 20-amp branch circuits installed in kitchens including butler’s pantries, dishwashers and disposal, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sun rooms, recreation rooms, closets, hallways, laundry areas and similar rooms or areas. Arc-fault circuit interrupters shall be installed in readily accessible locations. (NEC 210.12)
B. Whenever a branch circuit wiring is modified, replaced, or extended in any of the areas specified in 55A above, the branch circuit shall be protected by one of the following: (NEC 210.12(B))
- A combination-type AFCI circuit breaker located at the origin of the branch circuit
- A receptacle AFCI located at the first receptacle outlet of the existing branch circuit.
- At least one wall switch-controlled lighting outlet shall be installed in every habitable room, bathroom, kitchen, hallway, stairways, attached garage, detached garage and assessor building with electric power, and at the exterior side of each outdoor exit door having grade level access. Attics, under floor spaces, utility rooms and basements containing equipment or used for storage must be provided with a switch operated light. (NEC 210.70)
- Smoke alarms shall comply with UL 217 and UL 2034. Smoke alarms are to be powered by the building’s wiring with battery backup and shall be interconnected so the actuation of one alarm will activate all alarms in the dwelling unit. Interconnection of smoke alarms shall not be required where alterations or repairs do not result in removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection without the removal of interior finishes. Smoke alarms shall be permitted to be battery operated where installed in buildings without commercial power. Smoke alarms shall be installed in the following locations (IRC R314):
A. In each sleeping room.
B. Outside each sleeping area in the immediate vicinity of the bedrooms.
C. One on each additional story including basements and habitable attics.
D. Smoke alarms shall be installed not less than 3 feet horizontally from the door or opening of the bathroom that contains a bathtub or shower unless this would prevent placement of a smoke alarm in locations listed above.
E. In the hallway and in the room open to the hallway in dwelling units where the ceiling height of a room open to a hallway serving bedrooms exceeds that of the hallway by 24 inches or more.
A Carbon Monoxide alarms shall comply with UL 2034 and UL 217. Carbon Monoxide alarms are required in a single-family dwelling that has fuel-fired appliance(s), or an attached garage. The alarm must be installed within 15-feet of the entrance to each sleeping room (State of Colorado requirement) and must be listed by a nationally recognized, independent lab. Where a fuel-burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide alarm shall be installed within the bedroom. Plugs into a dwelling’s electrical outlet and has a battery backup. They may be combined with a smoke-detecting device if the combined device complies with applicable law. (IRC R315)
- Clothes closet lighting shall be limited surface-mounted or recessed incandescent fixtures with completely enclosed lamps, surface-mounted or recessed fluorescent fixtures, surface-mounted fluorescent or LED luminaires identified as suitable for installation within the closet storage space.
Surface mounted and recessed fixtures shall be installed on the wall above the door or on the ceiling with the following clearances between the fixture and the nearest point of a storage space as follows (NEC 410.16):
A. Incandescent fixtures or LED shall have a minimum 12-inch clearance.
B. Fluorescent fixtures shall have minimum 6-inch clearance.
C. Recessed incandescent or LED luminaires with completely enclosed light source shall have a minimum of 6” clearance.
E. Recessed fluorescent fixtures shall have a minimum 6-inch clearance.
- Working space must be provided around energized equipment for servicing and maintenance. The minimum dimensions shall not be less than 36-inches in depth and 30-inches in width in front of the equipment. Working space shall extend to at least 6-feet, 6-inches above the floor. (NEC 110.26)
- Electrical fixtures installed in wet or damp locations shall be installed so that water cannot enter or accumulate in wiring compartments or other electrical parts. Fixtures installed in wet locations must be labeled “suitable for wet locations”. Fixtures installed in damp locations must be labeled “suitable for damp locations” or “suitable for wet locations”. Switches or circuit breakers located in wet locations or outdoors must be enclosed in a weatherproof enclosure. Outdoor receptacles must have a weatherproof enclosure and an in-use cover. (NEC 410.10(A), 404.4, 406.9(A))
Cord-connected fixtures, hanging fixtures, track lighting, pendants, and ceiling fans shall not be located within 3-feet horizontally and 8-feet vertically from the top of a tub or shower rim. (NEC 410.10(D))
- Swimming pools, fountains, hot tubs, spas, and hydro-massage “Jacuzzi” tubs and similar installations shall comply with all provisions of the IRC for the approval of bonding equipment and lighting. All 15 and 20 amp, single-phase 125-volt receptacles located within 20-feet of the inside walls of pools, outdoor spas and hot tubs shall be protected by a GFCI circuit. Motors and equipment must be accessible without damaging the building structure or building finish. (NEC 680)
- The reinforcing shell of the pool shell, metal forming shells, coping stones, deck, brackets of niche fixtures, metal fittings, and electrical equipment, located less than 5-feet horizontally and less than 12-feet above maximum water level of swimming pools and built in place hot tubs shall be bonded together. The parts specified above shall be connected to an equipotential bonding grid. (NEC 680.26)