Area Wells for Emergency Escape and Rescue Openings
Area Wells (R310.4)
An emergency escape and rescue opening where the bottom of the clear opening is below the adjacent grade shall be provided with an area well in accordance with Sections R310.4.1 through R310.4.4.
Minimum Size (R310.4.1)
The horizontal area of the area well shall be not less than 9 square feet (0.9 m2), with a horizontal projection and width of not less than 36 inches (914 mm). The size of the area well shall allow the emergency escape and rescue opening to be fully opened. Except when a ladder or steps are required by Section R310.4.2, they can encroach not more than 6 inches (152 mm) into the required dimensions of the area well.
Ladder and Steps (R310.4.2)
Area wells with a vertical depth of greater than 44 inches shall be equipped with an approved permanently affixed ladder or steps. The ladder or steps shall not be obstructed by the emergency escape and rescue opening where the window or door is in the open position. Ladders or steps required by this section shall not be required to comply with Section R311.7 for means of egress.
Ladders (R310.4.2.1)
Ladders and rungs shall have an inside width of not less than 12 inches (305 mm), shall project not less than 3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center vertically for the full height of the area well.
Steps (R310.4.2.2)
Steps shall have an inside width of not less than 12 inches (305 mm), a minimum tread depth of 5 inches (127 mm) and a maximum riser height of 18 inches (457 mm) for the full height of the area well.
Drainage (R310.4.3)
Area wells shall be designed for proper drainage by connecting to the building’s foundation drainage system required by Section R405.1. Except when a drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, as detailed in Table R405.1 (good drainage characteristics).
Bars, Grilles, Covers and Screens (R310.4.4)
Where bars, grilles, covers, screens or similar devices are placed over emergency escape and rescue openings, bulkhead enclosures or area wells that serve such openings, the minimum net clear opening size shall comply with Sections R310.2 through R310.2.2 and R310.4.1. Such devices shall be releasable or removable from the inside without the use of a key or tool or force greater than that required for the normal operation of the escape and rescue opening.